The Enervex ADC100 Fan & Damper Control comes with an external PDS. The PDS is a NO/NC switch that monitors the pressure in the chimney.
The ADC100 operates a chimney fan at a set speed to create and maintain proper mechanical draft at the outlet of a heating appliance(s). The control provides a 10-120 VAC signal to single phase fans, as well as a 0-10 VDC signal that can be used to control 3-phase fans by a variable frequency drive.
The ADC100 comes with an external PDS. The PDS is a NO/NC switch that monitors the pressure in the chimney. In case of inadequate draft, the PDS will open and if open for 15 seconds, the control will go into alarm mode and lock out the appliance until draft is restored.
The control features a manual and automatic adjustment mode which is selected via dipswitch. The PDS check function and manual or automatic reset function are also selected through a dipswitch.
An integrated damper relay allows a damper to be connected directly to the ADC100. The control ensures that the damper is fully open before allowing the appliance to operate by interlocking the damper end-switches to the control. In the event that the controller senses any mechanical failures, the control will initiate a retry sequence.
- Operation
- 0-10 VAC control signal and 10-120 VAC for variable speed
- Controls both 1x120V and 3x230V/460V fan (three-phase fans require an EDrive)
- Use
- Used to control draft in systems where modulation is not required
- Controls the speed of the fan to maintain proper pressure in the chimney
- For indoor installations only
- For use with RS fans
- Used to control the draft of a gas-fired appliances such as:
- Furnaces
- Fireplaces
- Pizza Ovens
- Stoves
- Material
- The enclosure is made of NEMA 1 rated ABS plastic
- Standard Equipment
- ADC 100 Control Box
- Includes an external PDS Proven Draft Switch
- Stack Probe
- 6' Silicone Tubing
- Listings
- The ADC100 Fan Control is ETL Listed in the U.S. and Canada:
- UL 508 Standard for Industrial Control Equipment (17th Ed.)
- CSA C22.2 No. 14-05- Standard for Industrial Control Equipment
- Warranty
- 2-Year Factory Warranty. Complete warranty conditions are available from ENERVEX Inc.
Additional Information
Specifications
| Volts | 1x120VAC |
| Amps | 7.0 |
| Operating Temperature (°F) | -4 to 122 |
| Control Signal (mA) | Max. 10 |
| Control Relay | Max. 120 VAC / 8A |
| Output (VAC / VDC) | 10-120 / 0-10 |
| Post Purge Time (min) | 0-3 |
| Alarm Delay Time (sec) | 15 |
| Product Height (in) | 6.3 |
| Product Width (in) | 9.6 |
| Product Depth (in) | 3.5 |
| Product Weight (lbs) | 2.6 |
| Stack Probe Height (in) | 4.25 |
| Stack Probe Length (in) | 3.50 |